Input / Output: 380/220V, 400/230V & 415/240V AC - 50/60Hz
Standard Permissible Input Voltage Window OptionsIn situations where there is a reasonably good mains supply, a Stabilizer offering an input variation swing of ±10 % or ±15% (S10 / S15 Models) will usually be more than acceptable, but in more remote locations, or countries where the national supply infrastructure is less developed, variations of ±20% or greater may be needed to be accommodated by the Stabilizer. TIP - The wider the permissible input voltage window you wish the Stabiliser to accomodate and the more accurate the voltage you require on the output, the more expensive the Stabiliser. So, when selecting the most appropriate and cost efficient model for your application, it pays to know the state of the utility mains supply on site and the designed input voltage tolerances of the load equipment you wish to protect.
|
|
Technology: |
Magnetic Induction Design - Brushless Oil Immersed |
||||||||||||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||||||||||
Output Voltage: |
Presettable for any voltage between 380/220V, 400/230V or 415/240V (Customer to Specify) – Three Phase 4 Wire (3 Phase + Neutral + G/E). |
||||||||||||||||||||||||||||||||||||||||||
The permissible input voltage window is relative to the pre-set output voltage. |
|||||||||||||||||||||||||||||||||||||||||||
Output Voltage Accuracy: |
± 1.5%, ± 3% or ± 5% - auto selection based on input voltage swing. |
||||||||||||||||||||||||||||||||||||||||||
Frequency: |
47 to 65 Hz |
||||||||||||||||||||||||||||||||||||||||||
Response Time: |
< 1.5 ms |
||||||||||||||||||||||||||||||||||||||||||
Correction Time: |
A 10% supply variation will be corrected to within 2.5% in typically 0.6 to 1 second - dependent on the reselected permissible input voltage swing and system rating. |
||||||||||||||||||||||||||||||||||||||||||
Efficiency: |
>97% |
||||||||||||||||||||||||||||||||||||||||||
Power Factor: |
Any Lagging to 0.95 leading |
||||||||||||||||||||||||||||||||||||||||||
Surge Ratings:
|
10 x max current rating for 2 seconds |
||||||||||||||||||||||||||||||||||||||||||
3 x max current rating for 1 minute |
|||||||||||||||||||||||||||||||||||||||||||
2 x max current rating for 5 minutes |
|||||||||||||||||||||||||||||||||||||||||||
Surge Suppression: |
TVSS - Protects loads against high energy Spikes and Transient Voltages |
||||||||||||||||||||||||||||||||||||||||||
Total Harmonic Distortion: |
< 1% |
||||||||||||||||||||||||||||||||||||||||||
Independent Phase Control: |
Maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance. |
||||||||||||||||||||||||||||||||||||||||||
Insulation Oil: |
Uninhibited Transformer Oil conforming to BS EN 60296 (2004). |
||||||||||||||||||||||||||||||||||||||||||
Environment: |
Temperature Range -15°to 45° C |
||||||||||||||||||||||||||||||||||||||||||
|
Derate by 2% for each additional °C up to max 60°C |
||||||||||||||||||||||||||||||||||||||||||
|
Suitable for indoor tropical use 95% RH (non-condensing) |
||||||||||||||||||||||||||||||||||||||||||
|
Maximum altitude 1000m. Derate by 2.5% for each additional 500m. |
||||||||||||||||||||||||||||||||||||||||||
Paint Colour: |
RAL 7032 (Grey - Powder Coat) |
||||||||||||||||||||||||||||||||||||||||||
Construction: |
Enclosures to IP20 (NEMA 1 Style), BS EN 60529 |
||||||||||||||||||||||||||||||||||||||||||
Conformance: |
Complies with BS EN 55022 and the relevant parts of BS EN 61000 series of standards |
||||||||||||||||||||||||||||||||||||||||||
CE Conformity: |
CE Marked - being fully compliant with European Union Directives 2004/108/EC (replaced EMC Directive 89/336/EEC from July 2009) and 2006/95/EC (The Low Voltage Directive in force from January 2007) |
||||||||||||||||||||||||||||||||||||||||||
Standard Warranty: |
Two (2) Years / Twenty Four (24) Months from date of supply. Extendable, by purchasing an Extended Warranty, to Five (5) Years / Sixty (60 Months). |
||||||||||||||||||||||||||||||||||||||||||
Standard Features: |
Loss of Phase and Phase Reversal Alarm |
||||||||||||||||||||||||||||||||||||||||||
Over Temerature Alarm |
|||||||||||||||||||||||||||||||||||||||||||
Over Voltage and Low Voltage Alarms |
|||||||||||||||||||||||||||||||||||||||||||
Voltmeter / Phase Selector Switch |
|||||||||||||||||||||||||||||||||||||||||||
Ammeter / Phase Selector Switch |
|||||||||||||||||||||||||||||||||||||||||||
No-Volt Free Contacts (N.C & N.O) |
|||||||||||||||||||||||||||||||||||||||||||
Lightning Surge Arrestors |
|||||||||||||||||||||||||||||||||||||||||||
Oil Pressure Release Valve |
|||||||||||||||||||||||||||||||||||||||||||
Supplied Oil Filled |
|||||||||||||||||||||||||||||||||||||||||||
Optional Add-On Features: |
Earth Fault Relay Alarm |
||||||||||||||||||||||||||||||||||||||||||
Optional Main System Switch Board (MSB): |
Main System Switch Board - with Input Circuit, Output Circuit Breaker, Manual Maintenenace Bypass Switch & Metering and Interlocking Protection. 3 Pole as standard, with 4 Pole option. |
||||||||||||||||||||||||||||||||||||||||||
Optional Outdoor Enclosure: |
OIVSI SERIES - IVSI Stabilisers housed in refurbished 20 ft / 40 ft ISO Containers - suitable for outdoor / external environments. Please contact us for further details. |
||||||||||||||||||||||||||||||||||||||||||
|
|
||||||||||||||||||||||||||||||||||||||||||
Please Note – These Stabilisers are not designed to support / protect voltage “back feed” applications, where energy is required to be also fed back into the utility supply. |
Model: |
RATING |
AMPS (Per Phase) |
Dimensions |
Weight |
||
|
kVA |
@380V |
@400V |
@415V |
W x H x D(mm) |
(Kgs) |
IVSI-500H-3P-S10 |
500 |
759 |
721 |
695 |
2575 x 1598 x 930 |
2200 |
IVSI-750H-3P-S10 |
750 |
1139 |
1082 |
1043 |
2575 x 1688 x 930 |
2700 |
IVSI-1000H-3P-S10 |
1000 |
1518 |
1443 |
1390 |
2575 x 1818 x 930 |
3000 |
IVSI-1250H-3P-S10 |
1250 |
1898 |
1803 |
1738 |
2575 x 1848 x 930 |
3450 |
IVSI-1500H-3P-S10 |
1500 |
2278 |
2164 |
2086 |
2875 x 1780 x 1180 |
4200 |
IVSI-2000H-3P-S10 |
2000 |
3037 |
2885 |
2781 |
2875 x 1900 x 1380 |
5320 |
IVSI-2500H-3P-S10 |
2500 |
3797 |
3607 |
3447 |
2875 x 1900 x 1460 |
6400 |
IVSI-3000H-3P-S10 |
3000 |
4556 |
4328 |
4172 |
2965 x 2006 x 1620 |
8380 |
Note: | Other voltage configurations available upon enquiry / order. |
Optional Accessories added may affect dimensions and weights - subject to confirmation. |
Model: |
RATING |
AMPS (Per Phase) |
Dimensions |
Weight |
||
|
kVA |
@380V |
@400V |
@415V |
W x H x D(mm) |
(Kgs) |
IVSI-500H-3P-S15 |
500 |
759 |
721 |
695 |
2575 x 1598 x 930 |
2400 |
IVSI-750H-3P-S15 |
750 |
1139 |
1082 |
1043 |
2575 x 1818 x 930 |
3000 |
IVSI-1000H-3P-S15 |
1000 |
1518 |
1443 |
1390 |
2575 x 1848 x 930 |
3450 |
IVSI-1250H-3P-S15 |
1250 |
1898 |
1803 |
1738 |
2875 x 1780 x 1180 |
4200 |
IVSI-1500H-3P-S15 |
1500 |
2278 |
2164 |
2086 |
2875 x 1780 x 1320 |
4600 |
IVSI-2000H-3P-S15 |
2000 |
3037 |
2885 |
2781 |
2875 x 1900 x 1460 |
6400 |
IVSI-2500H-3P-S15 |
2500 |
3797 |
3607 |
3447 |
2965 x 1956 x 1620 |
7600 |
IVSI-3000H-3P-S15 |
3000 |
4556 |
4328 |
4172 |
2965 x 2006 x 1620 |
8820 |
Note: | Other voltage configurations available upon enquiry / order. |
Optional Accessories added may affect dimensions and weights - subject to confirmation. |
Model: |
RATING |
AMPS (Per Phase) |
Dimensions |
Weight |
||
|
kVA |
@380V |
@400V |
@415V |
W x H x D(mm) |
(Kgs) |
IVSI-500H-3P-S20 |
500 |
759 |
721 |
695 |
2575 x 1668 x 930 |
2700 |
IVSI-750H-3P-S20 |
750 |
1139 |
1082 |
1043 |
2575 x 1848 x 930 |
3450 |
IVSI-1000H-3P-S20 |
1000 |
1518 |
1443 |
1390 |
2875 x 1780 x 1180 |
4200 |
IVSI-1250H-3P-S20 |
1250 |
1898 |
1803 |
1738 |
2875 x 1780 x 1320 |
4600 |
IVSI-1500H-3P-S20 |
1500 |
2278 |
2164 |
2086 |
2875 x 1900 x 1380 |
5320 |
IVSI-2000H-3P-S20 |
2000 |
3037 |
2885 |
2781 |
2875 x 1956 x 1620 |
7600 |
IVSI-2500H-3P-S20 |
2500 |
3797 |
3607 |
3447 |
2965 x 2006 x 1620 |
8380 |
IVSI-3000H-3P-S20 |
3000 |
4556 |
4328 |
4172 |
2965 x 2150 x 1510 |
10000 |
Note: | Other voltage configurations available upon enquiry / order. |
Optional Accessories added may affect dimensions and weights - subject to confirmation. |
Model: |
RATING |
AMPS (Per Phase) |
Dimensions |
Weight |
||
|
kVA |
@380V |
@400V |
@415V |
W x H x D(mm) |
(Kgs) |
IVSI-500H-3P-S25 |
500 |
759 |
721 |
695 |
2575 x 1818 x 930 |
3000 |
IVSI-750H-3P-S25 |
750 |
1139 |
1082 |
1043 |
2575 x 1870 x 1180 |
4200 |
IVSI-1000H-3P-S25 |
1000 |
1518 |
1443 |
1390 |
2875 x 1780 x 1320 |
4600 |
IVSI-1250H-3P-S25 |
1250 |
1898 |
1803 |
1738 |
2875 x 1900 x 1380 |
5320 |
IVSI-1500H-3P-S25 |
1500 |
2278 |
2164 |
2086 |
2875 x 1900 x 1460 |
6400 |
IVSI-2000H-3P-S25 |
2000 |
3037 |
2885 |
2781 |
2875 x 2006 x 1620 |
8380 |
IVSI-2500H-3P-S25 |
2500 |
3797 |
3607 |
3447 |
2965 x 2150 x 1510 |
10000 |
Note: | Other voltage configurations available upon enquiry / order. |
Optional Accessories added may affect dimensions and weights - subject to confirmation. |
Model: |
RATING |
AMPS (Per Phase) |
Dimensions |
Weight |
||
|
kVA |
@380V |
@400V |
@415V |
W x H x D(mm) |
(Kgs) |
IVSI-500H-3P-S30 |
500 |
759 |
721 |
695 |
2575 x 1848 x 930 |
3600 |
IVSI-750H-3P-S30 |
750 |
1139 |
1082 |
1043 |
2575 x 1780 x 1320 |
4800 |
IVSI-1000H-3P-S30 |
1000 |
1518 |
1443 |
1390 |
2875 x 1900 x 1380 |
5600 |
IVSI-1250H-3P-S30 |
1250 |
1898 |
1803 |
1738 |
2875 x 1900 x 1460 |
6400 |
IVSI-1500H-3P-S30 |
1500 |
2278 |
2164 |
2086 |
2965 x 1956 x 1620 |
7600 |
IVSI-2000H-3P-S30 |
2000 |
3037 |
2885 |
2781 |
2965 x 2150 x 1510 |
10000 |
IVSI-2500H-3P-S30 |
2500 |
3797 |
3607 |
3447 |
2965 x 2150 x 1510 |
10500 |
Note: | Other voltage configurations available upon enquiry / order. |
Optional Accessories added may affect dimensions and weights - subject to confirmation. |
IVSI-HD-3P-S Series - 500 to 3000 kVA Input / Output: 380V, 400V & 415V AC - 50/60Hz In situations where there is a reasonably good mains supply, a Stabilizer offering an input variation swing of ±10 % or ±15% (S10 / S15 Models) will usually be more than acceptable, but in more remote locations, or countries where the national supply infrastructure is less developed, variations of ±20% or greater may be needed to be accommodated by the Stabilizer. TIP - The wider the permissible input voltage window you wish the Stabiliser to accomodate and the more accurate the voltage you require on the output, the more expensive the Stabiliser. So, when selecting the most appropriate and cost efficient model for your application, it pays to know the state of the utility mains supply on site and the designed input voltage tolerances of the load equipment you wish to protect. To obtain a personal price, or to discuss further how we might be able to help your organisation, please feel free Model: RATING AMPS (Per Phase) Dimensions Weight kVA @380V @400V @415V W x H x D(mm) (Kgs) IVSI-500HD-3P-S* 500 759 721 695 Dimensions, Weights and precise Standard and Optional Add-On Features as per the relevant S* model data sheet (see Technical Specification TAB below) or upon request. IVSI-750HD-3P-S* 750 1139 1082 1043 IVSI-1000HD-3P-S* 1000 1518 1443 1390 IVSI-1250HD-3P-S* 1250 1898 1803 1738 IVSI-1500HD-3P-S* 1500 2278 2164 2086 IVSI-2000HD-3P-S* 2000 3037 2885 2781 IVSI-2500HD-3P-S* 2500 3797 3607 3447 IVSI-3000HD-3P-S* 3000 4556 4328 4172 Technology: Magnetic Induction Design - Brushless Oil Immersed 380V or 400V or 415V – Three Phase 3 Wire (3 Phase + G/E - NO Neutral) Output Voltage Accuracy ±1.5% ±3% ±5% Ratings *S10 Models - Input Window ± 10% -12% /+13% -14% /+16% 500 to 3000 kVA *S15 Models – Input Window ± 15% -17% /+18% -19% /+21% 500 to 3000 kVA *S20 Models – Input Window ± 20% -22% / +23% -24% / +26% 500 to 3000 kVA *S25 Models – Input Window ± 25% -27% / +28% -29% / +31% 500 to 2500 kVA *S30 Models – Input Window ± 30% -32% / +33% -34% / +36% 500 to 2500 kVA Output Voltage: Presettable for any voltage between 380V, 400V or 415V (Customer to Specify) – Three Phase 3 Wire (3 Phase + G/E - NO Neutral). The permissible input voltage window is relative to the pre-set output voltage. Output Voltage Accuracy: ± 1.5%, ± 3% or ± 5% - auto selection based on input voltage swing. Frequency: 47 to 65 Hz Response Time: < 1.5 ms Correction Time: A 10% supply variation will be corrected to within 2.5% in typically 0.6 to 1 second - dependent on the reselected permissible input voltage swing and system rating. Efficiency: >97% Power Factor: Any Lagging to 0.95 leading Surge Ratings: 10 x max current rating for 2 seconds 3 x max current rating for 1 minute 2 x max current rating for 5 minutes Surge Suppression: TVSS - Protects loads against high energy Spikes and Transient Voltages Total Harmonic Distortion: < 1% Independent Phase Control: Maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance. Insulation Oil: Uninhibited Transformer Oil conforming to BS EN 60296 (2004). Environment: Temperature Range -15°to 45° C Derate by 2% for each additional °C up to max 60°C Suitable for indoor tropical use 95% RH (non-condensing) Maximum altitude 1000m. Derate by 2.5% for each additional 500m. Paint Colour: RAL 7032 (Grey - Powder Coat) Construction: Enclosures to IP20 (NEMA 1 Style), BS EN 60529 Conformance: Complies with BS EN 55022 and the relevant parts of BS EN 61000 series of standards CE Conformity: CE Marked - being fully compliant with European Union Directives 2004/108/EC (replaced EMC Directive 89/336/EEC from July 2009) and 2006/95/EC (The Low Voltage Directive in force from January 2007) Standard Warranty: Two (2) Years / Twenty Four (24) Months from date of supply. Extendable, by purchasing an Extended Warranty, to Five (5) Years / Sixty (60 Months). Standard Features: Loss of Phase and Phase Reversal Alarm Over Temerature Alarm Over Voltage and Low Voltage Alarms Voltmeter / Phase Selector Switch Ammeter / Phase Selector Switch No-Volt Free Contacts (N.C & N.O) Lightning Surge Arrestors Oil Pressure Release Valve Supplied Oil Filled Earth Fault Relay Alarm Optional Main System Switch Board (MSB): Main System Switch Board - with Input Circuit, Output Circuit Breaker, Manual Maintenenace Bypass Switch & Metering and Interlocking Protection. 3 Pole as standard, with 4 Pole option. Optional Outdoor Enclosure: OIVSI SERIES - IVSI Stabilisers housed in refurbished 20 ft / 40 ft ISO Containers - suitable for outdoor / external environments. Please contact us for further details. Please Note – These Stabilisers are not designed to support / protect voltage “back feed” applications, where energy is required to be also fed back into the utility supply.Introduction
Three Phase Oil Immersed Magnetic Induction 3 Wire (No Neutral) AC Voltage Stabilisers
Standard Permissible Input Voltage Window Options
Downloads
General Series Catalogue:
MSB Data Sheet:
Guide Specification:
Pricing
to either e-mail us
or call us on +44 (0)870 240 6162
Model Ratings (kVA/Amps)
S* = Selected permissible input voltage window - S10 (±10%), S15 (±15%), S20 (±20%), S25 (±25%) or S30 (±30%)
General Technical Specification
Optional Add-On Features:
Copyright © Ashley-Edison (UK) reserves the right to change any or all of the specifications indicated or implied without prior notice. E&OE
IVSI-H-3P-S-X468 Series - 500 to 3000 kVA Input / Output: 440/254V, 460/265V & 480/277V AC - 50/60Hz In situations where there is a reasonably good mains supply, a Stabilizer offering an input variation swing of ±10 % or ±15% (S10 / S15 Models) will usually be more than acceptable, but in more remote locations, or countries where the national supply infrastructure is less developed, variations of ±20% or greater may be needed to be accommodated by the Stabilizer. TIP - The wider the permissible input voltage window you wish the Stabilizer to accomodate and the more accurate the voltage you require on the output, the more expensive the Stabilizer. So, when selecting the most appropriate and cost efficient model for your application, it pays to know the state of the utility mains supply on site and the designed input voltage tolerances of the load equipment you wish to protect. To obtain a personal price, or to discuss further how we might be able to help your organisation, please feel free Model: RATING AMPS (Per Phase) Dimensions Weight kVA @440V @460V @480V W x H x D(mm) (Kgs) IVSI-500H-3P-S*-X468 500 655 627 601 Dimensions, Weights and precise Standard and Optional Add-On Features as per the relevant S* model data sheet (see Technical Specification TAB below) or upon request. IVSI-750H-3P-S*-X468 750 983 941 901 IVSI-1000H-3P-S*-X468 1000 1311 1254 1202 IVSI-1250H-3P-S*-X468 1250 1639 1568 1503 IVSI-1500H-3P-S*-X468 1500 1967 1882 1803 IVSI-2000H-3P-S*-X468 2000 2623 2509 2404 IVSI-2500H-3P-S*-X468 2500 3279 3137 3006 IVSI-3000H-3P-S*-X468 3000 3935 3764 3607 Technology: Magnetic Induction Design - Brushless Oil Immersed 440/254V or 460/265V or 480/277V – Three Phase 4 Wire (3 Phase + Neutral + G/E) Output Voltage Accuracy ±1.5% ±3% ±5% Ratings *S10 Models - Input Window ± 10% -12% /+13% -14% /+16% 500 to 3000 kVA *S15 Models – Input Window ± 15% -17% /+18% -19% /+21% 500 to 3000 kVA *S20 Models – Input Window ± 20% -22% / +23% -24% / +26% 500 to 3000 kVA *S25 Models – Input Window ± 25% -27% / +28% -29% / +31% 500 to 2500 kVA *S30 Models – Input Window ± 30% -32% / +33% -34% / +36% 500 to 2500 kVA Output Voltage: Presettable for any voltage between 440/254V or 460/265V or 480/277V (Customer to Specify) – Three Phase 4 Wire (3 Phase + Neutral + G/E). The permissible input voltage window is relative to the pre-set output voltage. Output Voltage Accuracy: ± 1.5%, ± 3% or ± 5% - auto selection based on input voltage swing. Frequency: 47 to 65 Hz Response Time: < 1.5 ms Correction Time: A 10% supply variation will be corrected to within 2.5% in typically 0.6 to 1 second - dependent on the reselected permissible input voltage swing and system rating. Efficiency: >97% Power Factor: Any Lagging to 0.95 leading Surge Ratings: 10 x max current rating for 2 seconds 3 x max current rating for 1 minute 2 x max current rating for 5 minutes Surge Suppression: TVSS - Protects loads against high energy Spikes and Transient Voltages Total Harmonic Distortion: < 1% Independent Phase Control: Maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance. Insulation Oil: Uninhibited Transformer Oil conforming to BS EN 60296 (2004). Environment: Temperature Range -15°to 45° C Derate by 2% for each additional °C up to max 60°C Suitable for indoor tropical use 95% RH (non-condensing) Maximum altitude 1000m. Derate by 2.5% for each additional 500m. Paint Colour: RAL 7032 (Grey - Powder Coat) Construction: Enclosures to IP20 (NEMA 1 Style), BS EN 60529 Conformance: Complies with BS EN 55022 and the relevant parts of BS EN 61000 series of standards CE Conformity: CE Marked - being fully compliant with European Union Directives 2004/108/EC (replaced EMC Directive 89/336/EEC from July 2009) and 2006/95/EC (The Low Voltage Directive in force from January 2007) Standard Warranty: Two (2) Years / Twenty Four (24) Months from date of supply. Extendable, by purchasing an Extended Warranty, to Five (5) Years / Sixty (60 Months). Standard Features: Loss of Phase and Phase Reversal Alarm Over Temerature Alarm Over Voltage and Low Voltage Alarms Voltmeter / Phase Selector Switch Ammeter / Phase Selector Switch No-Volt Free Contacts (N.C & N.O) Lightning Surge Arrestors Oil Pressure Release Valve Supplied Oil Filled Earth Fault Relay Alarm Optional Main System Switch Board (MSB): Main System Switch Board - with Input Circuit, Output Circuit Breaker, Manual Maintenenace Bypass Switch & Metering and Interlocking Protection. 3 Pole as standard, with 4 Pole option. Optional Outdoor Enclosure: OIVSI SERIES - IVSI Stabilisers housed in refurbished 20 ft / 40 ft ISO Containers - suitable for outdoor / external environments. Please contact us for further details. Please Note – These Stabilisers are not designed to support / protect voltage “back feed” applications, where energy is required to be also fed back into the utility supply.Introduction
Three Phase Oil Immersed Magnetic Induction AC Voltage Stabilizers
Standard Permissible Input Voltage Window Options
Downloads
General Series Catalog:
MSB Data Sheet:
Guide Specification:
Pricing
to either e-mail us
or call us on +44 (0)870 240 6162
Model Ratings (kVA/Amps)
S* = Selected permissible input voltage window - S10 (±10%), S15 (±15%), S20 (±20%), S25 (±25%) or S30 (±30%)
General Technical Specification
Optional Add-On Features:
Copyright © Ashley-Edison (UK) reserves the right to change any or all of the specifications indicated or implied without prior notice. E&OE
IVSI-HD-3P-S-X468 Series - 500 to 3000 kVA Input / Output: 440V, 460V & 480V AC - 50/60Hz In situations where there is a reasonably good mains supply, a Stabilizer offering an input variation swing of ±10 % or ±15% (S10 / S15 Models) will usually be more than acceptable, but in more remote locations, or countries where the national supply infrastructure is less developed, variations of ±20% or greater may be needed to be accommodated by the Stabilizer. TIP - The wider the permissible input voltage window you wish the Stabilizer to accomodate and the more accurate the voltage you require on the output, the more expensive the Stabilizer. So, when selecting the most appropriate and cost efficient model for your application, it pays to know the state of the utility mains supply on site and the designed input voltage tolerances of the load equipment you wish to protect. To obtain a personal price, or to discuss further how we might be able to help your organisation, please feel free Model: RATING AMPS (Per Phase) Dimensions Weight kVA @440V @460V @480V W x H x D(mm) (Kgs) IVSI-500HD-3P-S*-X468 500 655 627 601 Dimensions, Weights and precise Standard and Optional Add-On Features as per the relevant S* model data sheet (see Technical Specification TAB below) or upon request. IVSI-750HD-3P-S*-X468 750 983 941 901 IVSI-1000HD-3P-S*-X468 1000 1311 1254 1202 IVSI-1250HD-3P-S*-X468 1250 1639 1568 1503 IVSI-1500HD-3P-S*-X468 1500 1967 1882 1803 IVSI-2000HD-3P-S*-X468 2000 2623 2509 2404 IVSI-2500HD-3P-S*-X468 2500 3279 3137 3006 IVSI-3000HD-3P-S*-X468 3000 3935 3764 3607 Technology: Magnetic Induction Design - Brushless Oil Immersed 440V or 460V or 480V – Three Phase 3 Wire (3 Phase + G/E - NO Neutral) Output Voltage Accuracy ±1.5% ±3% ±5% Ratings *S10 Models - Input Window ± 10% -12% /+13% -14% /+16% 500 to 3000 kVA *S15 Models – Input Window ± 15% -17% /+18% -19% /+21% 500 to 3000 kVA *S20 Models – Input Window ± 20% -22% / +23% -24% / +26% 500 to 3000 kVA *S25 Models – Input Window ± 25% -27% / +28% -29% / +31% 500 to 2500 kVA *S30 Models – Input Window ± 30% -32% / +33% -34% / +36% 500 to 2500 kVA Output Voltage: Presettable for any voltage between 440V, 460V or 480V (Customer to Specify) – Three Phase 3 Wire (3 Phase + G/E - NO Neutral). The permissible input voltage window is relative to the pre-set output voltage. Output Voltage Accuracy: ± 1.5%, ± 3% or ± 5% - auto selection based on input voltage swing. Frequency: 47 to 65 Hz Response Time: < 1.5 ms Correction Time: A 10% supply variation will be corrected to within 2.5% in typically 0.6 to 1 second - dependent on the reselected permissible input voltage swing and system rating. Efficiency: >97% Power Factor: Any Lagging to 0.95 leading Surge Ratings: 10 x max current rating for 2 seconds 3 x max current rating for 1 minute 2 x max current rating for 5 minutes Surge Suppression: TVSS - Protects loads against high energy Spikes and Transient Voltages Total Harmonic Distortion: < 1% Independent Phase Control: Maintains each phase voltage stable irrespective of load unbalance, even up to 100% load unbalance. Insulation Oil: Uninhibited Transformer Oil conforming to BS EN 60296 (2004). Environment: Temperature Range -15°to 45° C Derate by 2% for each additional °C up to max 60°C Suitable for indoor tropical use 95% RH (non-condensing) Maximum altitude 1000m. Derate by 2.5% for each additional 500m. Paint Colour: RAL 7032 (Grey - Powder Coat) Construction: Enclosures to IP20 (NEMA 1 Style), BS EN 60529 Conformance: Complies with BS EN 55022 and the relevant parts of BS EN 61000 series of standards CE Conformity: CE Marked - being fully compliant with European Union Directives 2004/108/EC (replaced EMC Directive 89/336/EEC from July 2009) and 2006/95/EC (The Low Voltage Directive in force from January 2007) Standard Warranty: Two (2) Years / Twenty Four (24) Months from date of supply. Extendable, by purchasing an Extended Warranty, to Five (5) Years / Sixty (60 Months). Standard Features: Loss of Phase and Phase Reversal Alarm Over Temerature Alarm Over Voltage and Low Voltage Alarms Voltmeter / Phase Selector Switch Ammeter / Phase Selector Switch No-Volt Free Contacts (N.C & N.O) Lightning Surge Arrestors Oil Pressure Release Valve Supplied Oil Filled Earth Fault Relay Alarm Optional Main System Switch Board (MSB): Main System Switch Board - with Input Circuit, Output Circuit Breaker, Manual Maintenenace Bypass Switch & Metering and Interlocking Protection. 3 Pole as standard, with 4 Pole option. Optional Outdoor Enclosure: OIVSI SERIES - IVSI Stabilisers housed in refurbished 20 ft / 40 ft ISO Containers - suitable for outdoor / external environments. Please contact us for further details. Please Note – These Stabilisers are not designed to support / protect voltage “back feed” applications, where energy is required to be also fed back into the utility supply.Introduction
Three Phase Oil Immersed Magnetic Induction 3 Wire (No Neutral) AC Voltage Stabilizers
Standard Permissible Input Voltage Window Options
Downloads
General Series Catalog:
MSB Data Sheet:
Guide Specification:
Pricing
to either e-mail us
or call us on +44 (0)870 240 6162
Model Ratings (kVA/Amps)
S* = Selected permissible input voltage window - S10 (±10%), S15 (±15%), S20 (±20%), S25 (±25%) or S30 (±30%)
General Technical Specification